Multi-Function Power Meter
View Large
Product Name : Multi-Function Power Meter
Product Origin : China Taiwan
Product Category : Chitai
More Products : Click here!
Contact Details : 運揚有限公司 WANCO LIMITED
Product Code : CT1700
Product Details

The CT1700 is an instrument that measures, calculates and displays all main electrical parameters at any electrical network (balance or not). The measuring is true RMS value, through three AC voltage inputs and three AC current inputs (from Current Transformers ---/5A).


It was designed according to EMC and electrical safety standards, and manufactured under the ISO 9001 quality control. It is featured by its high measuring accuracy, its reduced size, and easy assembly mode and a yet economical price. It can be integrated into a communication network through its built-in-RS485/232 output by just using Modbus standard protocol. In addition, it provides two relay outputs (DO) and two alarm inputs (DI) for detection.


FEATURE


Harmonic distortion measurement THD-V & RTHD-A(31st)

Up to 21st harmonic analysis of V and ALCD back-light display2-alarm input (DI)2-alarm output (DO) V, A, W or DemandDemand measurement and alarm outputMeasurement of zero-phase currentPrecision True-RMS measurementRS485/232 communication interfacePT and CT scaling10-year memory for all setup and energy dataAuto calibration from computerMax, Min and Hold functionOutput DC 4 ~ 20mA and Pulse (option)96×96×158mm DIN case


SPECIFICATION


















































































































































































Display: 4 digits (9999) LCD back-light(V, A, W, VAR, PF, Hz)
5 digits (99999) LCD back-light(WH, VARH)
Accuracy: (at 23 ± 5℃ sine wave)
Voltage
± 0.1% of reading ± 0.1% of range

Current
± 0.1% of reading ± 0.1% of range

VA
± 0.2% of reading ± 0.2% of range

Watt
± 0.2% of reading ± 0.2% of range

Var
± 0.2% of reading ± 0.2% of range

Powe Factor
± 0.5% of reading

Watt Hour
± 0.2% of reading ± 1 count

Var Hour
± 0.2% of reading ± 1 count

Hz
± 0.05% of reading

Harmonic
± 0.2% of fundamental

Demand
± 0.4% of reading ± 0.2% of range

Max. input over capability
Amp. 10A continuous



50A for 5 sec.



Volt. 750V continuous

Conversion rate: (about)
about 1/sec.

Input burden
Volt. input ≦ 0.2 VA/phase



Amp. input ≦ 0.2 VA/phase

Over input indication
"OL"

Line voltage range
60V~700V

Phase voltage range
35V ~ 400V

Current range
20mA ~ 6A

Power factor range
±0.5~±1

Frequency range
45~65Hz

CT, PT scaling factors
1~9999

Setting for REF
0.001 ~ 1.000

Operating temp.
0~60℃

Storage temp.
-10~70℃

Temp. coefficient
≦100PPM/℃(≦60PPM/℃,25℃±10℃)

Max. relative humidity
95%

Dielectric strength
AC 2KV/1min. (input/output/power)


AC 2.8KV/1min. (input/output/power/case)

Surge test
4 KV/1.2 X 50μS, IEC 255-4

Dimensions
96×96×158mm

Mounting
Panel mounting

Protocol
MODBUS, RTU

Baud rate
9600/19200/38400

Address range
1~255

Watt-hour data back-up time
10 years

Aux. power
AC90~260V, 50/60Hz



DC24V, 48V, 110V±20% (option)

Power consumption
AC6VA, DC5W

Weight (about)
760g