View Large |
Product Name : | Multi-Function Power Meter |
Product Origin : | China Taiwan | |
Product Category : | Chitai | |
More Products : | Click here! | |
Contact Details : | 運揚有限公司 WANCO LIMITED | |
Product Code : | CT1700 |
The CT1700 is an instrument that measures, calculates and displays all main electrical parameters at any electrical network (balance or not). The measuring is true RMS value, through three AC voltage inputs and three AC current inputs (from Current Transformers ---/5A).
It was designed according to EMC and electrical safety standards, and manufactured under the ISO 9001 quality control. It is featured by its high measuring accuracy, its reduced size, and easy assembly mode and a yet economical price. It can be integrated into a communication network through its built-in-RS485/232 output by just using Modbus standard protocol. In addition, it provides two relay outputs (DO) and two alarm inputs (DI) for detection.
FEATURE
‧Harmonic distortion measurement THD-V & RTHD-A(31st)
‧Up to 21st harmonic analysis of V and A‧LCD back-light display‧2-alarm input (DI)‧2-alarm output (DO) V, A, W or Demand‧Demand measurement and alarm output‧Measurement of zero-phase current‧Precision True-RMS measurement‧RS485/232 communication interface‧PT and CT scaling‧10-year memory for all setup and energy data‧Auto calibration from computer‧Max, Min and Hold function‧Output DC 4 ~ 20mA and Pulse (option)‧96×96×158mm DIN case
SPECIFICATION
Display: 4 digits (9999) LCD back-light(V, A, W, VAR, PF, Hz) | |
5 digits (99999) LCD back-light(WH, VARH) | |
Accuracy: (at 23 ± 5℃ sine wave) | |
Voltage | ± 0.1% of reading ± 0.1% of range |
Current | ± 0.1% of reading ± 0.1% of range |
VA | ± 0.2% of reading ± 0.2% of range |
Watt | ± 0.2% of reading ± 0.2% of range |
Var | ± 0.2% of reading ± 0.2% of range |
Powe Factor | ± 0.5% of reading |
Watt Hour | ± 0.2% of reading ± 1 count |
Var Hour | ± 0.2% of reading ± 1 count |
Hz | ± 0.05% of reading |
Harmonic | ± 0.2% of fundamental |
Demand | ± 0.4% of reading ± 0.2% of range |
Max. input over capability | Amp. 10A continuous |
50A for 5 sec. | |
Volt. 750V continuous | |
Conversion rate: (about) | about 1/sec. |
Input burden | Volt. input ≦ 0.2 VA/phase |
Amp. input ≦ 0.2 VA/phase | |
Over input indication | "OL" |
Line voltage range | 60V~700V |
Phase voltage range | 35V ~ 400V |
Current range | 20mA ~ 6A |
Power factor range | ±0.5~±1 |
Frequency range | 45~65Hz |
CT, PT scaling factors | 1~9999 |
Setting for REF | 0.001 ~ 1.000 |
Operating temp. | 0~60℃ |
Storage temp. | -10~70℃ |
Temp. coefficient | ≦100PPM/℃(≦60PPM/℃,25℃±10℃) |
Max. relative humidity | 95% |
Dielectric strength | AC 2KV/1min. (input/output/power) |
AC 2.8KV/1min. (input/output/power/case) | |
Surge test | 4 KV/1.2 X 50μS, IEC 255-4 |
Dimensions | 96×96×158mm |
Mounting | Panel mounting |
Protocol | MODBUS, RTU |
Baud rate | 9600/19200/38400 |
Address range | 1~255 |
Watt-hour data back-up time | 10 years |
Aux. power | AC90~260V, 50/60Hz |
DC24V, 48V, 110V±20% (option) | |
Power consumption | AC6VA, DC5W |